Closed-Loop Control; Protection And Monitoring; Mtbf - Siemens SITOP 6EP1336-3BA00 Manual

Power supply, modular 1ph/2ph
Table of Contents

Advertisement

Technical data

6.4 Closed-loop control

6.4
Closed-loop control
Dyn. line regulation
(U
±15 %), max.
in rated
Dyn. load regulation
(I
: 50/100/50 %), U
±
out
out
typ.
Load step regulation time
50 to 100%, typ.
Load step regulation time
100 to 50%, typ.
Regulation time, max.
6.5

Protection and monitoring

Output overvoltage pro-
tection
Current limitation, typ.
Property of the output:
short-circuit proof
Short-circuit protection
Continuous short-circuit
current: rms value, typ.
Overload / short-circuit
display
6.6

MTBF

Mean Time Between Fail-
ures
48
6EP1333-3BA10
6EP1334-3BA10
(24 V/5 A)
(24 V/10 A)
0.1 %
0.1 %
3 %
3 %
2 ms
2 ms
2 ms
2 ms
5 ms
5 ms
6EP1333-3BA10
6EP1334-3BA10
(24 V/5 A)
(24 V/10 A)
< 35 V
< 35 V
5.5 A
12 A
Yes
Optional constant current characteristic curve or latching shutdown
5.5 A
12 A
Yellow LED for "overload", red LED for "latching shutdown"
6EP1333-3BA10 (24 V/5 A)
6EP1334-3BA10 (24 V/10 A)
6EP1336-3BA00 (24 V/20 A)
6EP1337-3BA00 (24 V/40 A)
SN29500: > 500000 h (typ. 700000 h) at 40 °C, rated load, 24 hour operation
6EP1336-3BA00
6EP1337-3BA00
(24 V/20 A)
(24 V/40 A)
1 %
1 %
2 %
2 %
2 ms
2 ms
2 ms
2 ms
5 ms
5 ms
6EP1336-3BA00
6EP1337-3BA00
(24 V/20 A)
(24 V/40 A)
< 35 V
< 35 V
23 A
46 A
23 A
46 A
Manual, 04.2018, C98130-A7548-A1-4-7629
SITOP modular 1ph/2ph

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents