Table 3-2 Default Settings For Operation Using The Bop - Siemens Micromaster 440 Operating Instructions Manual

0.12 kw - 250 kw
Hide thumbs Also See for Micromaster 440:
Table of Contents

Advertisement

Issue 12/02
3.2.2.1
Commissioning with the BOP
NOTICE
♦ The BOP motor control functions are disabled by default. To control the motor
via the BOP, parameter P0700 should be set to 1 and P1000 set to 1.
♦ The BOP can be fitted to and removed from the inverter whilst power is
applied.
♦ If the BOP has been set as the I/O control (P0700 = 1), the drive will stop if
the BOP is removed.
Table 3-2
Parameter
P0100
P0307
P0310
P0311
P1082
ATTENTION
MICROMASTER 440 can only be operated with one of the operator panels BOP
or AOP.
If a BOP-2 panel is used
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
You can alter parameter values via the BOP. To set
parameters on this panel, you must remove the SDP and
attach the BOP (see Appendix A).
The BOP features a five-digit, seven-segment display for
showing parameter numbers and values, alarm and fault
messages and setpoints and actual values. Parameter
sets cannot be saved via the BOP.
Table 3-2 shows the factory default settings for operation
via the BOP.
Default settings for operation using the BOP
Meaning
Operating Mode Europe/US
Power (rated motor)
Motor frequency rating
Motor speed rating
Maximum Motor Frequency
Default Europe (North America)
50 Hz, kW (60Hz, hp)
Dimension (kW (Hp)) depending on setting of P0100.
[Value depending on variant.]
50 Hz (60 Hz)
1395 (1680) rpm [depending on variant]
50 Hz (60 Hz)
will be displayed
3 Commissioning
49