International English
Warnings and faults states on the Status Display Panel
The two LEDs on the Status Display Panel indicate the operating status of your inverter.
These LEDs also indicate various warnings or fault states. In section 6.1 the inverter
states, indicated by the two LEDs are explained.
3.1.2
Basic operation with SDP
With the SDP fitted, the following is possible:
Controlling the speed of the motor
Connect the terminals as shown in the figure below.
Figure 3-2
Note
The terminal layout for connecting power and control cables is shown in the photographs
on the inside of the back cover of this manual.
3.1.3
Commissioning with the Basic Operator Panel (BOP)
150.00
Hz
1
0
Table 3-2
Parameter
30
Start and stopping the motor
Reversing the motor
Fault Reset
DIN1
DIN2
DIN3
24V+
5
6
7
8
Start/Stop Rev
Ack
Digital Inputs
Basic operation with SDP
The Basic Operator Panel (BOP), which is available as an
option, provides access to the inverter parameters and enables
you to customize the settings of your MICROMASTER 420. The
BOP can be used to configure several MICROMASTER 420
Inverters. There is no need to purchase a separate BOP for each
inverter.
Fn
It should be noted that the BOP motor control functions are
disabled by default. To control the motor via the BOP, parameter
Jog
P
P0700 should be set to 1.
Table 3-2 shows the factory default settings for operation via the
Basic Operator Panel.
Default settings for operation using the BOP
Meaning
P0100
Operating Mode Europe/US
P0307
Power (rated motor)
P0310
Motor frequency rating
P0311
Motor speed rating
P1082
Maximum Motor Frequency
0V
10V+
0V
AIN+
AIN-
9
1
2
3
4
9
5.0 k
Analogue Inputs
3. COMMISSIONING
Default Europe (North America)
50 Hz, kW (60Hz, hp)
kW (Hp)
50 Hz (60 Hz)
1395 (1680) rpm
[depending on variant]
50 Hz (60 Hz)
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0