Table 3-1 Default Settings For Operation Using The Sdp - Siemens Micromaster 440 Operating Instructions Manual

0.12 kw - 250 kw
Hide thumbs Also See for Micromaster 440:
Table of Contents

Advertisement

3 Commissioning
3.2.1
Commissioning with the SDP
In addition, the following conditions must be met:
! Linear V/f motor speed controlled by an analog potentiometer.
! Maximum speed 1500 rpm at 50 Hz (1800 rpm at 60 Hz); can be controlled by
a potentiometer via the analog inputs of the inverter.
! Ramp acceleration time/ramp deceleration time = 10 s
Settings for more complex applications can be found in the parameter list and in
Section 3.2.2 "Commission Overview with BOP or AOP".
Table 3-1
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
46
The SDP has two LEDs on the front which display the
current operating status of the inverter (see Section 6.1).
When the SDP is used, the presettings of the inverter
must be compatible with the following motor data:
! Rated motor power
! Motor voltage
! Rated motor current
! Rated motor frequency
(A conventional Siemens motor is recommended)
Default settings for operation using the SDP
Terminals
5
6
7
8
16
17
Via AIN1
Via AIN2
Parameter
Default Operation
P0701 = '1'
ON right
P0702 = '12'
Reverse
P0703 = '9'
Fault Acknowledge
P0704 = '15'
Fixed Frequency
P0705 = '15'
Fixed Frequency
P0706 = '15'
Fixed Frequency
P0707 = '0'
Inactive
P0708 = '0'
Inactive
MICROMASTER 440
Issue 12/02
Operating Instructions
6SE6400-5AW00-0BP0