Siemens Micromaster 440 Operating Instructions Manual page 53

0.12 kw - 250 kw
Hide thumbs Also See for Micromaster 440:
Table of Contents

Advertisement

Issue 12/02
Flow chart Quick Commissioning (QC)
P0003 User access level
1
Standard
2
Extended
3
Expert
P0010 Start Quick Commissioning
0
Ready to Run
1
Ready to Run
30 Factory Setting
P0100 Operation for Europe/N. America
0
Power in kW; f default 50 Hz
1
Power in hp; f default 60 Hz
2
Power in kW; f default 60 Hz
NOTE
Settings 0 and 1 should be changed using the DIP
switches to allow permanent setting. The DIP
switches should be used to create permanent
settings. After a mains break the DIP switch settings
overide the parameter settings.
P0205 Inverter application
0
Constant torque
1
Variable torque
Note
P0205 = 1 should only be used in applications with
quadratic characteristic (pumps, fans)
P0300 Select motor type
1
Asynchronous rotational motor
2
Synchronous rotational motor
Note
With P0300 = 2 the control parameters are disabled
P0304 Rated Motor Voltage
Setting range: 10 V - 2000 V
Nominal motor voltage (V) from rating plate.
P0305 Rated Motor Current
Setting range: 0 - 2 x inverter rated current (A)
Nominal motor current (A) from rating plate.
P0307 Rated Motor Power
Setting range: 0.01 kW - 2000 kW
Nominal motor power (kW) from rating plate.
If P0100 = 1, values will be in hp.
1) Motor-specific parameters – see motor rating plate.
2) The parameters offer more setting options than listed here. See Parameter List for further setting options.
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
2)
1
2)
1
1
3
2
1)
1
1)
1
1)
1
Access level
P0308 Rated motor cosPhi
Setting range: 0.000 - 1.000
Nom. motor power factor (cosPhi) from rating plate .
Visible only when P0100 = 0, 2, (motor power in kW).
P0309 Rated motor efficiency
Setting range: 0.0 - 99.9 %
Nominal motor efficiency in % from rating plate. .
Visible only when P0100 = 1, ( motor power in hp).
P0310 Rated Motor Frequency
Setting range: 12 Hz - 650 Hz
Nominal motor frequency (Hz) from rating plate.
P0311 Rated Motor Speed
Setting range: 0 - 40.000 U/min
Nominal motor speed (rpm) from rating plate.
P0320 Motor magnetizing current
Setting range: 0.0 - 99.0 %
Motor magnetizing current (%) relative to the rated
motor current (P0305).
P0335 Motor cooling
0
Self-cooled
1
Force-cooled
2
Self-cooled and internal fan
3
Force-cooled and internal fan
P0640 Motor overload factor
Setting range: 10.0 - 400.0 %
Motor overload current limit [%] relative to P0305
(rated motor current).
P0700 Selection of Command Source
0
Factory Setting
1
BOP / AOP
2
Terminals (Digital Inputs)
Note
If P0700 = 2 is selected, the function of the digital
inputs can be determind via P0701 to P0708. P0701
to P0708 = 99 enables the BICO-parameterization for
the digital inputs.
3 Commissioning
1)
2
1)
2
1)
1
1)
1
3
2
2
2)
1
53