Issue 12/02
F0041 Motor Data Identification Failure
Possible Causes
Motor data identification failed.
Fault value = 0: Load missing
Percentage values based on the impedance Zb = Vmot,nom / sqrt(3) / Imot,nom
Diagnose & Remedy
! Fault value = 0:
! Fault value = 1-40: Check if motor data in P0304 to P0311 are correct
Check what type of motor wiring is required (star, delta).
F0042 Speed Control Optimisation Failure
Possible Causes
Speed control optimisation (P1960) failed
Fault value = 0: Time out waiting for stable speed
= 1: Inconsistent readings
F0051 Parameter EEPROM Fault
Possible Causes
Read or write failure while saving non-volatile parameter
Diagnose & Remedy
1. Factory Reset and new parameterization
2. Contact Customer Support / Service Department
F0052 Power stack Fault
Possible Causes
Read failure for power stack information or invalid data
Diagnose & Remedy
Hardware defect, contact Customer Support / Service Department
F0053 IO EEPROM Fault
Possible Causes
Read failure for IO EEPROM information or invalid data
Diagnose & Remedy
1. Check data
2. Change IO board
MICROMASTER 440
6SE6400-5AW00-0BP0
1: Current limit level reached during identification.
2: Identified stator resistance less than 0.1 % or greater than 100 %.
3: Identified rotor resistance less than 0.1 % or greater than 100 %.
4: Identified stator reactance less than 50 % and greater than 500 %
5: Identified main reactance less than 50 % and greater than 500 %
6: Identified rotor time constant less than 10 ms or greater than 5 s
7: Identified total leakage reactance less than 5 % and greater than 50 %
8: Identified stator leakage reactance less than 25 % and greater than 250 %
9: Identified rotor leakage inductance less than 25 % and greater than 250 %
20: Identified IGBT on-voltage less than 0.5 V or greater than 10 V
30: Current controller at voltage limit
40: Inconsistency of identified data set, at least one identification failed
Check that the motor is connected to the inverter
Operating Instructions
6 Troubleshooting
OFF2
OFF2
OFF2
OFF2
OFF2
95