3 Commissioning
P1000 Selection of Frequency Setpoint
1 Motor potentiometer setpoint
2 Analog setpoint 1
3 Fixed frequency setpoint
7 Analog setpoint 2
Note
For setting a additional setpoint see Parameter List.
If P1000 = 1 or 3 the selection depends on the
settings of P0700 to P0708.
P1080 Min. Motor Frequency
Setting range: 0 - 650 Hz
Sets minimum motor frequency (0 - 650 Hz) at which
the motor will run irrespective of the frequency set-
point. The value is valid for both motor directions.
P1082 Max. Motor Frequency
Setting range: 0 - 650 Hz
Sets maximum motor frequency (0 - 650 Hz) at which
the motor will run irrespective of the frequency set-
point. The value is valid for both motor directions.
P1120 Ramp-Up Time
Setting range: 0 - 650 s
Time taken for the motor to accelerate from standstill
up to maximum motor frequency.
P1121 Ramp-Down Time
Setting range: 0 - 650 s
Time taken for motor to decelerate from maximum
motor frequency down to standstill.
P1135 OFF3 ramp-down time
Setting range: 0 - 650 s
Defines the ramp down time from the maximum
frequency to standstill for the OFF3 command.
P1300 Control mode
0
V/f with linear charac.
1
V/f with FCC
2
V/f with parabolic charac.
3
V/f with programmable charac.
5
V/f for textile applications
6
V/f with FCC for textile applications
19 V/f control with independent voltage setpoint
20 Sensorless vector control
21 Vector control with sensor
22 Sensorless vector torque-control
23 Vector torque-control with sensor
Note
Vector control modes can only be used together with
an asynchronous motor
2) The parameters offer more setting options than listed here. See Parameter List for further setting options.
54
2)
P1500 Selection of torque setpoint
1
0
No main setpoint
2
Analog setpoint
4
USS on BOP link
5
USS on COM link
6
CB on COM link
7
Analog setpoint 2
Note
For setting a additional setpoint see Parameter List.
P1910 Select motor data identification
1
0
Disabled
1
Identification of all parameters with
parameter change.
2
Identification of all parameters without
parameter change.
3
Identification of saturation curve with
1
parameter change.
4
Identification of saturation curve without
parameter change.
Note
Motor identification must be performed with a cold
motor (20 °C). If the ambient temperature is not
within the range of 20°C (+5°C), P0625 Ambient
1
motor temperature must be updated.
P1910 = 0
1
P3900 End Quick Commissioning
0
End Quick Commissioning without
motor calculation or factory reset.
2
1
End Quick Commissioning with motor
calculation and factory reset.
2
End Quick Commissioning with motor
calculation and with I/O reset.
3
End Quick Commissioning with motor
calculation but without I/O reset.
2
P3900 = 1,2
Quick Commissioning complete, the inverter goes
into ready-to-run state
Alarm A0541
Motor data idendification active.
Switch on Motor, Motor data identification
starts. After completing motor identifi-
cation, Alarm message A0541 disappears.
If the motor shall be operated with field
weakening, the operation is to repeat with
P1910 = 3 "saturation curve".
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
Issue 12/02
2)
2
2)
2
P1910 = 1,2,3,4
1
P3900 = 3