Field Wiring Connections

Grounding the Module
In solid-state control systems, grounding and wire routing helps limit the effects of noise due to
electromagnetic interference (EMI). Run the ground connection from the ground screw of the
controller to the ground bus prior to connecting any devices. Use AWG #14 wire. For
AC-powered controllers, this connection must be made for safety purposes.
You must also provide an acceptable grounding path for each device in your application. For
more information on proper grounding guidelines, refer to the Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.
EXPLOSION HAZARD
WARNING
• In Class I, Division 2 applications, the bus connector must be fully seated and
• In Class I, Division 2 applications, all modules must be mounted in direct
ATTENTION
To comply with the CE Low Voltage Directive (LVD), all connected I/O must be
powered from a source compliant with the Safety Extra Low Voltage (SELV) or
Protected Extra Low Voltage (PELV).
WARNING
If you connect or disconnect wiring while the field-side power is on, an electrical
arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
the bus connector cover must be snapped in place.
contact with each other as shown on page 10. If DIN rail mounting is used, an
end anchor must be installed ahead of the controller and after the last 1762
I/O module.
MicroLogix 1762-IQ32T DC Input Module
Publication 1762-IN019B-EN-P - June 2013
11