Allen-Bradley MicroLogix 1762-IQ32T Installation Instructions Manual page 19

Dc input module
Table of Contents

Advertisement

Environmental Specifications
Attribute
EFT/B immunity
Surge transient immunity
Conducted RF immunity
Derating Charts for each input
point
5.4W
32
5.2W
31
28
24
23
26
30
Certifications
Certification (when
(1)
product is marked)
c-UL-us
CE
C-Tick
KC
(1)
See the Product Certification link at
Conformity, Certificates, and other certification details.
Value
IEC 61000-4-4:
±2 kV at 5 kHz on signal ports
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
@Vin=26.4V
4.8W
4.1W
3.9W
40
55
60
°C
44917
Value
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File
E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for
U.S. and Canada. See UL File E194810.
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Korean Registration of Broadcasting and Communications Equipment,
compliant with:
Article 58-2 of Radio Waves Act, Clause 3
http://www.rockwellautomation.com/products/certification
MicroLogix 1762-IQ32T DC Input Module
point
6.8W
32
5.1W
4.8W
24
22
19
18
20
30
Publication 1762-IN019B-EN-P - June 2013
@Vin=30.0V
4.1W
3.9W
40
55 60
°C
44918
for Declaration of
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents