FLASHSCAN™ INTELLIGENT FEATURES
• Poll up to 318 devices on each loop in less than two sec-
onds.
• Activate up to 159 outputs in less than five seconds.
• Multicolor LEDs blink device address during Walk Test.
• Fully
digital,
high-precision
5,539,389).
• Manual sensitivity adjustment — nine levels.
• Pre-alarm ONYX intelligent sensing — nine levels.
• Sensitivity levels:
– Ion – 0.5 to 2.5%/foot obscuration.
– Photo – 0.5 to 2.35%/foot obscuration.
– Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.
– Acclimate Plus™ – 0.5 to 4.0%/foot obscuration.
– IntelliQuad – 1.0 to 4.0%/foot obscuration.
– IntelliQuad™ PLUS – 1.0 to 4.0%/foot obscuration
• Drift compensation (U.S. Patent 5,764,142).
• Multi-detector algorithm involves nearby detectors in alarm
decision (U.S. Patent 5,627,515).
• Automatic detector sensitivity testing (NFPA-72 compliant).
• Maintenance alert (two levels).
• Self-optimizing pre-alarm.
• Programmable activation of sounder/relay bases during
alarm or pre-alarm.
• Read Status displays the level of detector cleanliness.
Sample System Options
CPU2-3030D
display or
CPU2-3030ND
Shown in CAB-C4 with display
DVC audio in CA-1 in second tier
NOTE: CPU2-3030 firmware version 14.0 (and higher) can support LCD-160 on the RDP port, or LCD2-80/LCD-80 in terminal mode,
but not both at the same time.
Page 2 of 8 — DN-7070:H • 12/19/2011
protocol
(U.S.
Patent
FAPT-851
FSL-751
FSP-851
...etc.
NFS2-3030
FSL-751 VIEW® (VERY INTELLIGENT EARLY WARN-
ING) SMOKE DETECTION TECHNOLOGY
• Revolutionary spot laser design.
• Advanced ONYX intelligent sensing algorithms differentiate
between smoke and non-smoke signals (U.S. Patent
5,831,524).
• Addressable operation pinpoints the fire location.
• No moving parts to fail or filters to change.
• Early warning performance comparable to the best aspira-
tion systems at a fraction of the lifetime cost.
FAPT-851 ACCLIMATE PLUS™ LOW-PROFILE INTELLI-
GENT MULTI-SENSOR
• Detector automatically adjusts sensitivity levels without
operator intervention or programming. Sensitivity increases
with heat.
• Microprocessor-based technology; combination photo and
thermal technology.
• Low-temperature signal at 40°F ± 5°F (4.44°C ± 2.77°C).
FSC-851 INTELLIQUAD
ADVANCED MULTI-CRITERIA DETECTOR
• Detects all four major elements of a fire (smoke, heat, CO,
and flame).
• Automatic drift compensation of smoke sensor and CO cell.
• High nuisance-alarm immunity.
• Six sensitivity levels.
NBG-12LX FMM-1 FRM-1
PRN Series
Printer
XP6/10 I/O
Modules

Hide quick links: