Banner DX80G9M6S-P2 Quick Start Manual

Banner DX80G9M6S-P2 Quick Start Manual

Surecross performance gateway, configurable gateway with discrete and analog i/o

Advertisement

Quick Links

SureCross Performance Gateway
Configurable Gateway with discrete and analog I/O
For complete technical information about this product, including dimensions, accessories, and specifications, see
Models
Frequency
DX80G9M6S-P2
900 MHz ISM Band
DX80G2M6S-P2
2.4 GHz ISM Band
DX80...C (IP20; NEMA 1) models are also available. To order this model with an IP20 housing, add a C to the end of the model number:
DX80G9M6S-P2C.
SureCross User Configuration Tool

Setting Up Your Wireless Network

To set up and install your wireless network, follow these steps:
1.
Configure the DIP switches of all devices.
2.
Connect the sensors to the SureCross devices.
3.
Apply power to all devices.
4.
Form the wireless network by binding the Nodes to the Gateway. If the binding instructions are not included in the datasheet, refer to the product manual for binding
instructions.
5.
Observe the LED behavior to verify the devices are communicating with each other.
6.
Conduct a site survey between the Gateway and Nodes. If the site survey instructions are not included in this datasheet, refer to the product manual for detailed site
survey instructions.
7.
Install your wireless sensor network components. If installation instructions are not included in this datasheet, refer to the product manual for detailed installation
instructions.
For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accessories, refer to one of the following
product manuals.
• SureCross Quick Start Guide: Banner part number
P/N 155861 Rev. D
WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing
so could lead to serious injury or death. This device does NOT include the
self-checking redundant circuitry necessary to allow its use in personnel safety
applications. A sensor failure or malfunction can cause either an energized or
de-energized sensor output condition.
CAUTION: Never Operate 1 Watt Radios Without Antennas
To avoid damaging the radio circuitry, never power up SureCross Performance
or SureCross MultiHop (1 Watt) radios without an antenna.
Environmental Rating
I/O
Inputs: Four selectable discrete, two 0–20 mA or 0–10V analog
IP67, NEMA 6
Outputs: Four sourcing discrete, two 0–20mA analog
The User Configuration Tool (UCT) offers an easy way to link I/O points in your wireless network,
view I/O register values graphically, and set system communication parameters when a host system
is not part of the wireless network.
The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for 1 Watt radios, BWA-
HW-006 can be used for all other radios) converter cable to pass information between your comput-
er and the Gateway. Download the most recent revisions of the UCT software from Banner Engi-
neering's website: http://www.bannerengineering.com/wireless.
128185
3/14/2013
www.bannerengineering.com
and search for 155861_web
0 155861
2

Advertisement

Table of Contents
loading

Summary of Contents for Banner DX80G9M6S-P2

  • Page 1: Setting Up Your Wireless Network

    The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for 1 Watt radios, BWA- HW-006 can be used for all other radios) converter cable to pass information between your comput- er and the Gateway. Download the most recent revisions of the UCT software from Banner Engi- neering's website: http://www.bannerengineering.com/wireless.
  • Page 2: Configuring The Dip Switches

    SureCross Performance Gateway • SureCross Wireless I/O Network Manual: 132607 • Web Configurator Manual (used with "Pro" and DX83 models): 134421 • Host Configuration Manual 132114 Configuring the DIP Switches Before making any changes to the DIP switch positions, disconnect the power. For devices with batteries integrated into the housing, remove the battery for at least one minute.
  • Page 3 • Non-Performance radios must be set to use Extended Address Mode (DIP switch 1 ON) For more detailed instructions about setting up your wireless network, refer to the Quick Start Guide, Banner document number 128185. For more information about using Performance and non-Performance radios within the same network, refer the technical note titled Mixing Performance Radios and 150 mW Radios in the Same Net- worklisted on the FAQ/Knowledgebase section of Banner's Wireless Sensor Networks website.
  • Page 4 SureCross Performance Gateway Wire No. Wire Color Description Brown 10 to 30V dc White RS485 / D1 / B / + Blue dc common (GND) Black RS485 / D0 / A / – Gray Comms Gnd Terminal Block (IP67) This is the terminal block for the DX80**M6S-P2 models. AIx or Ax.
  • Page 5: Led Behavior For The Gateways

    SureCross Performance Gateway Discrete Input Wiring for PNP Sensors Discrete Input Wiring for NPN Sensors 10-30V dc dc common Wiring Diagrams for Discrete Outputs Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.
  • Page 6: Modbus Register Table

    SureCross Performance Gateway LED 1 LED 2 Gateway Status Modbus Communication Active (flashing yellow) Modbus Communication Error (flashing red) For Gateway and Ethernet Bridge systems, active Modbus communication refers to the communication between the Gateway and the Ethernet Bridge. For GatewayPro systems, the Modbus communication LEDs refer to the communication internal to the GatewayPro.
  • Page 7 Banner Engineering could void the user’s authority to operate the product. All specifications published in this document are subject to change. Banner reserves the right to modify product specifications or to update documentation at any time. For the most recent version of any documentation, refer to: www.bannerengineering.com.
  • Page 8: Banner Engineering Corp Limited Warranty

    Banner Engineering Corp Limited Warranty Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period.

This manual is also suitable for:

Dx80g2m6s-p2