Danfoss VLT HVAC Drive FC 102 Operating Instructions Manual page 107

315-1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

General Specifications
1) For type of fuse see section Fuses.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to
variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to
the power loss in the frequency converter and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to
30W to the losses. (Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B,
each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be
allowed for (+/-5%).
MG16B202
Operating Instructions
Danfoss A/S © Rev. 06/2014 All rights reserved.
7
7
105