Danfoss VLT HVAC Drive FC 102 Operating Instructions Manual page 80

315-1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

How to Programme
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1]
Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
[167]
Start command activ
[168]
Hand / Off
[169]
Auto mode
[180]
Clock Fault
[181]
Prev. Maintenance
[188]
AHF Capacitor Connect
6
6
[189]
External Fan Control
[190]
No-Flow
[191]
Dry Pump
[192]
End Of Curve
[193]
Sleep Mode
[194]
Broken Belt
[195]
Bypass Valve Control
[196]
Fire Mode
[197]
Fire Mode was Act.
[198]
Drive Bypass
[211]
Cascade Pump 1
[212]
Cascade Pump 2
[213]
Cascade Pump 3
6-00 Live Zero Timeout Time
Range:
10 s
[1 -
*
99 s]
6-01 Live Zero Timeout Function
Option:
78
Function:
Function:
Enter the live zero time-out time period. Live zero
time-out time is active for analog inputs, that is,
terminal 53 or terminal 54, used as reference or
feedback sources. If the reference signal value
associated with the selected current input drops
below 50% of the value set in
parameter 6-10 Terminal 53 Low Voltage,
6-12 Terminal 53 Low Current,
parameter 6-20 Terminal 54 Low Voltage or
6-22 Terminal 54 Low Current for a time period
longer than the time set in parameter 6-00 Live
Zero Timeout Time, the function selected in
parameter 6-01 Live Zero Timeout Function is
activated.
Function:
Select the time-out function. The function set
in parameter 6-01 Live Zero Timeout Function is
activated if the input signal on terminal 53 or
54 is below 50% of the value in
parameter 6-10 Terminal 53 Low Voltage,
6-12 Terminal 53 Low Current,
parameter 6-20 Terminal 54 Low Voltage or
6-22 Terminal 54 Low Current for a time period
Danfoss A/S © Rev. 06/2014 All rights reserved.
Operating Instructions
6-01 Live Zero Timeout Function
Option:
[0]
Off
*
[1]
Freeze
output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and
trip
Par 6-xx
High Ref./
Feedb. Value'
Par 6-xx
Low Ref./
Feedb. Value'
Illustration 6.12 Live Zero Conditions
6-10 Terminal 53 Low Voltage
Range:
0.07 V
*
Function:
defined in parameter 6-00 Live Zero Timeout
Time. If several time-outs occur simultaneously,
the frequency converter prioritises the time-
out functions as follows
1.
Parameter 6-01 Live Zero Timeout
Function
2.
8-04 Control Timeout Function
The output frequency of the frequency
converter can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent
trip
Ref./Feedback
[RPM]
1500
1200
900
600
300
150
1 V
5 V
Par 6-xx
'Low Voltage'or
'Low Current'
Par 6-xx
'High Voltage'or
'High Current'
Function:
[ 0 - par.
Enter the low-voltage value. This analog
6-11 V]
input scaling value should correspond to
the low reference/feedback value set in
parameter 6-14 Terminal 53 Low Ref./Feedb.
Value.
10 V
[V]
Analog input
MG16B202