Warnings and Alarms
2 = Second frequency converter from the left
inverter module in enclosure size F14.
3 = Right inverter module in enclosure sizes F12
or F13.
3 = Third from the left inverter module in
enclosure size F14.
4 = Far right inverter module in enclosure size
F14.
5 = Rectifier module.
6 = Right rectifier module in enclosure size F14.
ALARM 246, Power card supply
This alarm is only for enclosure size F frequency converters.
It is equivalent to Alarm 46. The report value in the alarm
log indicates which power module generated the alarm:
1 = Left most inverter module.
2 = Middle inverter module in enclosure sizes F12
or F13.
2 = Right inverter module in enclosure sizes F10
or F11.
2 = Second frequency converter from the left
inverter module in enclosure size F14.
3 = Right inverter module in enclosure sizes F12
or F13.
3 = Third from the left inverter module in
enclosure size F14.
4 = Far right inverter module in enclosure size
F14.
5 = Rectifier module.
6 = Right rectifier module in enclosure size F14.
ALARM 247, Power card temperature
This alarm is only for enclosure size F frequency converters.
It is equivalent to Alarm 69. The report value in the alarm
log indicates which power module generated the alarm:
1 = Left most inverter module.
2 = Middle inverter module in enclosure sizes F12
or F13.
2 = Right inverter module in enclosure sizes F10
or F11.
2 = Second frequency converter from the left
inverter module in enclosure size F14.
3 = Right inverter module in enclosure sizes F12
or F13.
3 = Third from the left inverter module in
enclosure size F14.
4 = Far right inverter module in enclosure size
F14.
5 = Rectifier module.
6 = Right rectifier module in enclosure size F14.
MG16B202
Operating Instructions
ALARM 248, Illegal power section configuration
This alarm is only for enclosure size F frequency converters.
It is equivalent to Alarm 79. The report value in the alarm
log indicates which power module generated the alarm:
WARNING 250, New spare part
A component in the frequency converter has been
replaced.
Troubleshooting
WARNING 251, New typecode
The power card or other components have been replaced
and the typecode changed.
Troubleshooting
Danfoss A/S © Rev. 06/2014 All rights reserved.
1 = Left most inverter module.
2 = Middle inverter module in enclosure sizes F12
or F13.
2 = Right inverter module in enclosure sizes F10
or F11.
2 = Second frequency converter from the left
inverter module in enclosure size F14.
3 = Right inverter module in enclosure sizes F12
or F13.
3 = Third from the left inverter module in
enclosure sizes F14.
4 =Ffar right inverter module in enclosure sizes
F14.
5 = Rectifier module.
6 = Right rectifier module in enclosure size F14.
Reset the frequency converter for normal
operation.
Reset to remove the warning and resume normal
operation.
8
8
117