5.15 NetAXS/NetAXS Access Controller Panel Connection Detail
Figure 33: NetAXS/NetAXS Access Controller Panel Connection Detail
To Serial Connection
DIP Switch Settings
S1-S5: Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
DO NOT
CONNECT
SHIELD
NetAXS Panel
485
Common
3
485 +
1
485 -
2
NetAXS TB7
NetAXS™ NX4L1 Access Control Unit Installation Guide, Document 7-901099V3
1
2
3
NetAXS TB7
DIP Switch Settings
S1-S5: Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
X
Shield
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
NetAXS™ NX4L1 Installation Guide
Ground Shield
X
DO NOT CONNECT or
GROUND SHIELD
1
NetAXS TB7
DIP Switch Settings
S1-S5: Panel Address
S6: OFF
J36: OPEN
J37: OPEN
Ground only one
side of cable shield
System Configuration
2
3
57