Figure B-2: RS-485 Wiring for NetAXS-4 Loop
To Serial Connection

4.0 RS-485 Wiring for a Mixed Loop

The 485+ (A) of one controller is connected to 485+ (A) of the next controller
using one wire of the first twisted pair.
The 485– (B) of one controller is connected to 485– (B) of the next controller
using the other wire of the first twisted pair.
On a loop that contains both NetAXS-123 and NetAXS panels (mixed loop), the
second pair of the wires are twisted together and connected to the RS-485 COM
on the next NetAXS-4 controller to the RS-485 COM of the next NetAXS-4
controller in the loop.
Do not connect the RS-485 COM on the NetAXS-123 controllers. The RS-485
COM is bypassed on the NetAXS-123 controller.
The shield is only connected on one end of the cable, not both.
See Figure B-3 on page 82.
NetAXS™ NX4L1 Access Control Unit Installation Guide, Document 7-901099V3
NetAXS TB7
DIP Switch Settings
S1-S5: Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
DO NOT
CONNECT
SHIELD
NetAXS Panel
Shield
485
Common
3
485 +
1
485 -
2
NetAXS TB7
Ground Shield
DO NOT CONNECT or
GROUND SHIELD
1
2
3
DIP Switch Settings
DIP Switch Settings
S1-S5: Panel Address
S1-S5: Panel Address
S6: OFF
S6: OFF
J36: CLOSED
J36: OPEN
J37: CLOSED
J37: OPEN
Ground only one
side of cable
shield
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
RS-485 Wiring for a Mixed Loop