5.14 N-485-PCI-2/NetAXS Access Controller Panel Connection Detail

This configuration has not been approved by UL.

Figure 32: N-485-PCI-2/NetAXS Access Controller Panel Connection Detail

To Serial Connection
See 485 interface
connection note
N-485-PCI-2
485 -
56
www.honeywell.com
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: ON
S7: ON
S8: OFF
1
NetAXS TB7
X
Shield
485
Common
485 +
485 Interface Connection Types
RS-485
N-485-PCI-2
N-485-HUB-2
N-485-PCI-2L
Ground Shield
DO NOT CONNECT or
GROUND SHIELD
2
3
DIP Switch Settings
DIP Switch Settings
S1-S5: Panel Address
S1-S5: Panel Address
S6: OFF
S6: OFF
J36: CLOSED
J36: OPEN
J37: CLOSED
J37: OPEN
Ground only one
side of cable shield
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
NetAXS Panel
COM Port
M-56K Modem
LANSRL100 or LANSRLU1
X
1
2
3
NetAXS TB7