5.11 M-56K Dial-up Modem, RS-485 Connection via NetAXS

This connection supports 31 NetAXS Access Controller panels for each drop line. It has not been
approved by UL.

Figure 29: M-56K Dial-up Modem, RS-485 Connection via NetAXS

Terminal
13
NetAXS™ NX4L1 Access Control Unit Installation Guide, Document 7-901099V3
COM Port
Female 9 Pin
(RX) 2
(TX) 3
(Comm) 5
CBL50
Male 9 Pin
NetAXS
Panel
DIP Switch Settings
S1-S5 Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
EG
DB 9 / DB 25 Connectors
Female
Male
13
1
25
25
14
5
1
5
1
9
6
9
6
FAX/MODEM
Straight Through Cable
Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)
Male 25 Pin
3 (RX)
2 (TX)
7 (Comm)
FAX/MODEM
Male 25 Pin
RS-232 (50 ft.)
Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)
RS-485 (4,000 ft.)
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
NetAXS
Panel
EG
RS-485 Cable
NetAXS Panels
1
TB7-1 (RS485+)
TB7-2 (RS485-)
14
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
NetAXS™ NX4L1 Installation Guide
M-56K
Analog
Phone
Line
Dedicated
analog
M-56K
phone
line
recommended
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: OPEN
J37: OPEN
NetAXS
Panel
EG
It is recommended to
Earth Ground (EG)
each NetAXS enclosure
Individually
System Configuration
See RS-485
Cable Note
EG
53