4.4 Reader Wiring

Each reader port supports a single 12-volt reader with Wiegand output format. Power
to the readers is shared with the AUX Power ports TB3 and TB14. The maximum
power draw is 600 mA for readers and AUX Power combined.
To fully utilize each reader port, a shielded 7-conductor cable (18–22 AWG) is
required. The reader buzzer feature is not supported with NetAXS-4. Therefore, you
can use the standard six-conductor cable. The cable shield should be grounded at the
panel only. Grounding at both ends can cause ground loops which can be disruptive.
The maximum recommended length of wiring is 500 feet per reader.

Table 2 Reader Wiring

TB5-1, 6-1, 11-1, 12-1
TB5-2 6-2, 11-2, 12-2
TB5-3, 6-3, 11-3, 12-3
TB5-4, 6-4, 11-4, 12-4
TB5-5, 6-5, 11-5, 12-5
TB5-6, 6-6, 11-6, 12-6
TB5-7, 6-7, 11-7, 12-7
Incorrect wiring of the reader to the panel can cause the panel to stop operating.
Note:
NetAXS™ NX4L1 Access Control Unit Installation Guide, Document 7-901099V3
lists the dimensions of the cabinet's conduit entries.
CONDUIT
1/2" (12.7 mm)
5
2
8
6
N/A
Terminal
Wire Color
Brown
Green
White
Black
Red
Variable
Variable
NetAXS™ NX4L1 Installation Guide
CONDUIT
CONDUIT 1"
3/4" (19.0 mm)
(25.4 mm)
5
N/A
2
N/A
8
N/A
6
N/A
N/A
Wiegand Reader
LED Control
Wiegand Data 0 or Data
Wiegand Data 1 or Clock
Common
12 VDC Power
Tamper
Buzzer
Installation
CONDUIT 2"
(50.8 mm)
2
2
N/A
N/A
2
N/A
27