5.2 RS-485 Connection via NetAXS

This connection supports thirty-one NetAXS Access Controller panels for each drop line. However,
because UL has approved the NetAXS panel only as a standalone system, the computer terminal and
NetAXS gateway panel appear in this illustration only to show the installation and programming of the
NetAXS panel.

Figure 19: RS-485 Connection via NetAXS

Terminal
NetAXS™ NX4L1 Access Control Unit Installation Guide, Document 7-901099V3
RS-232 (50 ft. max.)
COM Port
RS-485 Cable
NetAXS Panel
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
NetAXS
Getaway
DIP Switch Settings
S1-S5: Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 CLOSED
J37 CLOSED
NetAXS
Panel
EG
Only Earth Ground (EG)
EG
It is recommended to Earth Ground (EG)
each NetAXS enclosure individually
NetAXS™ NX4L1 Installation Guide
System Configuration
RS-485 (4,000 ft.)
Refer to NetAXS / NetAXS
Panel Connection Detail
diagram
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 OPEN
J37 OPEN
NetAXS
Panel
EG
See
RS-485
Cable
one side of cable
EG