Reader Wiring

The following Honeywell reader module numbers have been approved by UL for use with the
PW6K1R2: OM40BHONA, OM55BHONA, OP10HONE, OP30HONE, OP40HONE, OP90HONE,
OT30HONA, OT31HONA, OT35HONA, and OT36HONA.
Each reader port supports a reader with TTL interface. Power to the reader is selectable as 5VDC or
12VDC (pass-through). This selection is done by setting the jumpers J2 for reader 0 and J3 for reader
1. Set jumper at position "5" for 5VDC or "12" for pass-through 12VDC. The factory defaults set J2
and J3 to "5".
For wiring to a reader port:
Table 5: Settings for Wiring to a Reader Port
Terminal
1
2
3
4
5
6
The LED control terminal in each reader port can be configured via host software to support one-wire
single or bi-colored reader LED. An example of the most common configuration is shown below. If
Beeper Control is not used, its terminal can be programmed to be the second wire for the two-wire
bi-colored reader LED.
Table 6: Settings for Configuring an LED Control Terminal
LED Output->
Single Color LED
Bi-Color LED
To fully utilize each reader port, a 6-conductor cable (18AWG) is required. Reader port configuration
is set via host software.
PW-6000 Two-Reader Module Installation Guide, Document 800-01951, Revision C
Typical Wire Color
Wiegand Reader
Red
Power (5 or 12
Vdc)
Brown
LED control
Yellow
Beeper Control
White
Data 1 Signal
Green
Data 0 Signal
Black
Common
High
LED On
Green LED On
Installing the PW-6000 Two-Reader Module
Clock/Data Reader
Power (5 or 12 Vdc)
LED control
Beeper Control
Clock Signal
Data Signal
Common
Tri-Stated
Low
LED Off
LED Off
Both LEDs Off
Red LED On
Wiring