Environment; Cable; Table 10: Reader Wiring - Honeywell NetAXS-123 Installation Manual

Access control unit
Hide thumbs Also See for NetAXS-123:
Table of Contents

Advertisement

Installing the NetAXS-123 Panels
Hardware Specifications

5.6 Environment

• Temperature: 0C to 49C operating, -55C to +85C storage.
• Humidity: 5% to 85% RHNC.

5.7 Cable

Use industry-standard cables that meet the following specifications:

Table 10: Reader Wiring

Cable Specifications
Readers
Alarm Input
Relay Outputs
62
www.honeywell.com
Description
6 Conductor, Shielded
Twisted Pair, Shielded
Twisted Pair, Shielded
AWG
Maximum Distance:
Feet (Meters)
18
500 (153)
18
2,000 (610)
18
2,000 (610)