light blue. Selecting a station and then clicking Edit will display the Allocated Station Selection
screen.
Filter Station Runtime
Clicking on a filter station runtime item will select the runtime, changing the background of the
selected item to light blue. Selecting a runtime and then clicking Edit will display the Time Edit
screen.
Filter Bank Enabled
Filter Banks can be enabled or disabled. Clicking on the tick (cross) will change the Filter Bank to
disabled (enabled).
12.4

Filter Bank Advanced Parameters

Filter Parameters
The Filter Parameters screen is the first page of Advanced Filter Bank Parameters and is displayed
by pressing the
icon on the Filter Bank Edit screen.
Figure 52 - Filter Bank Advanced Parameters Edit - Page 1
In the example screen shown in Figure 52, the filter will ignore PD inputs for 20 seconds at the start
of irrigation and group changes. When the Filter PD input closes, the filter will operate for the run
times specified. At the end of the filter cycle, Filter PD inputs will be ignored for 10 minutes, to
prevent continuous filter operation. If a Filter PD input does not occur for 120 minutes during a single
irrigation, a filter cycle will commence. This prevents filter clogging due to faulty PD switches.