SPECIFICATIONS

Table 1: Line Mode Specifications
INVERTER MODEL
Input Voltage Waveform
Nominal Input Voltage
Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage
High Loss Return Voltage
Max AC Input Voltage
Nominal Input Frequency
Low Loss Frequency
Low Loss Return Frequency
High Loss Frequency
High Loss Return Frequency
Output Short Circuit
Protection
Max bypass current
Efficiency (Line Mode)
Transfer Time
Output power derating:
When AC input voltage drops to
95V, the output power will be
derated.
Sinusoidal (utility or generator)
65Vac± 7V (Appliances)
100Vac± 7V (UPS);
70Vac± 7V (Appliances)
50Hz / 60Hz (Auto-detection)
Line mode: Circuit Breaker
Battery mode: Electronic Circuits
>95% ( Rated R load, battery full charged )
10ms typical (UPS);
20ms typical (Appliances)
120Vac model:
Output Power
Rated Power
50% Power
24
3KVA
120Vac
95Vac± 7V (UPS)
140Vac± 7V
135Vac± 7V
150Vac
40± 1Hz
42± 1Hz
65± 1Hz
63± 1Hz
40A
65V
95V
140V
Input Voltage