When the device is turned off, the signaling contact is always activated (open).
Figure 4-3
4.1.6

SCALANCE X108 Button

What does the button do?
Using the button, you can display and modify the set fault mask.
After pressing the button, the currently valid fault mask is displayed for approximately 3
seconds. The LEDs of the monitored ports flash at a frequency of 5 Hz.
After 3 seconds the new fault mask is displayed. The flashing frequency is reduced to 2.5
Hz. After a further 3 seconds, the new fault mask is adopted and saved. The monitored ports
are indicated by permanently lit LEDs until the button is released.
As long as the LEDs are still flashing, the saving of the mask can be interrupted by releasing
the button.
If an empty fault mask is set (no port is monitored) or you want to set an empty mask, four 4
LEDs flash on and off alternating with their neighboring LEDs.
At the same time, you can also set the monitoring of the redundant power supply with the
fault mask. Monitoring of the power supply is activated only when both power supplies are
connected when the fault mask is saved.
The factory default is no port monitoring.
4.1.7

SCALANCE X108 LEDs

Fault indicator (red LED)
Status
lit red
not lit
Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line
Commissioning Manual, 1,
Signaling Contact SCALANCE X108
Meaning
The SCALANCE X108 detects an error. At the same time, the
signaling contact opens.
The following faults are detected:
1. Link down event on a monitored port
2. Failure of one of the two redundant power supplies.
No fault detected by the SCALANCE X108.