Scalance X206-1 Button - Siemens SCALANCE X-100 Commissioning Manual

Scalance industrial ethernet product line
Hide thumbs Also See for SCALANCE X-100:
Table of Contents

Advertisement

Product Characteristics
4.4 SCALANCE X206-1
Figure 4-12
The following errors/faults can be signaled by the signaling contact:
• The failure of a link at a monitored port.
• The failure of one of the two redundant power supplies.
The connection or disconnection of a communication node on an unmonitored port does not
lead to an error message.
The signaling contact remains activated until the error/fault is eliminated or until the current
status is applied as the new desired status using the button.
When the device is turned off, the signaling contact is always activated (open).
4.4.7

SCALANCE X206-1 Button

What does the button do?
Using the button, you can display and modify the set fault mask.
After pressing the button, the currently valid fault mask is displayed for approximately 3
seconds. The monitored ports flash at a frequency of 5 Hz.
After 3 seconds the new fault mask is displayed. The flashing frequency is reduced to 2.5
Hz. After a further 3 seconds, the new fault mask is adopted and saved. The monitored ports
are indicated by permanently lit LEDs until the button is released.
As long as the LEDs are still flashing, the saving of the mask can be interrupted by releasing
the button.
If an empty fault mask is set (no port is monitored) or you want to set an empty mask, four 4
LEDs flash on and off alternating with their neighboring LEDs.
At the same time, you can also set the monitoring of the redundant power supply with the
fault mask. Monitoring of the power supply is activated only when both power supplies are
connected when the fault mask is saved.
The factory default is no port monitoring.
If the button is pressed longer (15 seconds), the device is reset to "factory defaults". This is
indicated by all the Port LEDs flashing. During this activity, the device must not be turned off.
4-30
SCALANCE X206-1 Signaling Contact
Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line
Commissioning Manual, 1,

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scalance x-200

Table of Contents