Siemens SIMATIC PC 670 Equipment Manual page 148

Computing unit
Hide thumbs Also See for SIMATIC PC 670:
Table of Contents

Advertisement

Hardware Information
MPI/DP interface
The MPI/DP port on the computing unit is assigned as follows:
Figure 7-7
Pin
Short Name
No.
1
-
2
-
3
LTG_B
4
RTS_AS
5
M5EXT
6
P5 EXT
7
-
8
LTG_A
9
RTS_PG
Shield
7-16
1
6
9
5
PROFIBUS/MPI Socket Connector
Meaning
Not assigned
Not assigned
Signal lead B of MPI module
RTSAS, control signal for
received data stream. The signal
is '1' active when the directly
connected AS is sending.
M5EXT return line (GND) of the 5
V power supply. The current load
caused by an external user
connected between P5EXT and
M5EXT must not exceed 90 mA.
P5EXT supply (+5 V) of 5 V
supply. The current load caused
by an external user connected
between P5EXT and M5EXT
must not exceed 90 mA.
Not assigned
Signal lead A of MPI module
RTS output signal of the MPI
module. The signal is '1' when
the PG is sending.
On connector casing
Input/Output
-
-
Input/Output
Input
Output
Output
-
Input/Output
Output