TPS
7. Trouble shooting
Sensor status
Cause
Does not operate
Irregular supply voltage
as expected
Wire / cable cut or improperly connected
The red LEDs
Inappropriate installation
remain unlit
Trigger level too low
TPS installed too high
Irregular operation Dirty lens
Something swaying between the sensors
interrupts the light beam
The red LEDs blink
Trigger level set get too long
continuously
TPS installed too low
The red LEDs flicker
Minimum gap between devices too short
continuously
The device is interrupted by other infrared
emitters
Adjusting trigger
Beams are interrupted by a hand (LEDs
level (screws) has
always on)
no effect
Trigger level is too long (LEDs always off)
Trigger level cannot be set
Direction
Wrong TPS device
recognition
functions poorly in
Sensor incorrectly set
both directions
Direction
The two triggers do not have the same level Adjust the trigger to the same level
recognition
functions poorly in
one direction
If the problem persists, please contact your local CEDES representative (www.cedes.com).
8. Maintenance
Although TPS does not need periodical maintenance, a functional check with every facility maintenance check is strongly
recommended.
8.1
Periodic functional test
The periodic functional test should consist of the following:
Test the reopening function over the whole object area.
Confirm sensor is fastened securely
Ensure the front window / lenses of TPS are clean and without scratches
8.2
Cleaning
Clean the front surface from dust or dirt with a soft towel.
To clean the surface with a towel, it must be either dry or
slightly moist, but should not be wet.
© CEDES | V 1.6
Action
Adjust to the specified voltage range
Check the wires / cable:
Reconnect or replace as appropriate
Check the installation section (Chapter 5)
Increase the trigger level
Check the installation section (Chapter 5)
Clean the front surface from dust or dirt with
a soft towel
Remove the obstruction
Decrease the trigger level
Check the installation section (Chapter 5)
Increase gap between devices
If possible, change the alignment angle of
the sensors
Take care that while manually adjusting
the trigger level with a screwdriver, the light
beams are not interrupted by your hand
Try to pull the screw a bit while tightening
Ensure that there is a background
Check the label for right TPS device
Adjust the trigger to the same level
NOTICE
Damage to the sensor
Never
use
any
or
mechanically
highpressure water to clean the sensor.
English
solvents,
cleaners
abrasive
towels
or