Analog Output Signalling (proportional or 2-state): menu level 0

Analog mode (the loop-current) can provide either:
a 4 or 20 / 20 or 4 mA output, when 2-state mode is selected
or
a 4 to 20 / 20 to 4 mA continuous signal proportional to the percent of the range
Notes:
To set values for Upper and Lower Threshold Delay, and Upper and Lower
Threshold Setting (2-state mode), the loop-current menu (07) must be in 2-state
mode.
The factory setting is FailSafe High mode, and 2-state mode is selected.
When the loop-current control is in analog mode, the LCD displays only - - - - for
these menu selections (only applicable in FPM mode, selected at menu 1E).
Upper Threshold Delay (2-state mode)
The Upper Threshold Delay controls the Activation delay: the amount of time that has to
pass uninterrupted with the probe covered to a level above the Upper Threshold Setting
before the timer expires. When the timer expires, the output signal complies with the
setting from Menu 08 for a covered probe. Whenever the level drops below the Upper
Threshold Setting before the timer expires, the timer is restarted.
As an extra identifier, an upward running A is displayed to the right of the value.
Menu
Affected
Item
by:
03
07
1. Set the loop-current control (Menu 07) to 2-state mode.
2. Set the rotary switch to 3.
3. Press the RED (+) or BLUE(–) button to increase or decrease the value.
or: Press and hold a button to start a repeat function.
or: Press and hold both buttons simultaneously to toggle the value between
minimum (0) and maximum (100).
1.
When FSH/FSL mode is selected at menu 1E, the mA signal is either 20 or 4 mA
2.
The continuous mA signal is available only when FPM mode is selected at menu 1E.
7ML19985GG03
Rotary
Left
Switch
Mode
Arrow
Position
2-
state
3
Off
Analog
Pointek CLS500 – INSTRUCTION MANUAL
1
Added
Des-
Indicator
cription
Upward
Upper
running A at
Threshold
*
right of value
Delay
factory setting
2
Values
seconds
0.0
Display
shows
- - - -
Page 69