Keylock Level
Controls the access protection level for the device. The factory setting is a protection
level of 0, which places no restriction on modification of settings.
HART settings override local settings.
Notes:
If the HART setting is 0, there are no restrictions, and you cannot change the
protection to a higher level locally.
If the HART setting is 3, no changes can be made, and this protection level
cannot be changed locally.
Protection level 1 disables the ability to set a value by pressing two buttons
simultaneously.
Protection level 2 disables the ability to change a value by stepping it up or down.
Protection level 3 completely disables all changing of values.
Rotary
Menu
Switch
Item
Position
1F
F
1. Set the rotary switch to F.
2. Press the RED (+) or BLUE (–) button to change the setting.
Page 82
Protection
Left
Arrow
Level
On
* No restrictions
0
1
2
3
Pointek CLS500 – INSTRUCTION MANUA
local
Description
settings
PL 0
No restrictions
Disables 2-button
PL 1
adjustments
Disables 1-button
PL 2
adjustments
Disables all changes PL 3
Display
HART
settings
PH 0
PH 1
PH 2
PH 3