Siemens Pointek CLS500 Operating Instructions Manual page 86

Capacitance switches
Hide thumbs Also See for Pointek CLS500:
Table of Contents

Advertisement

Factory Settings
Displays whether the factory settings are still in place, or how much they have been
changed, and allows you to restore the factory settings.
Rotary
Menu
Switch
Item
Position
12
2
Set the rotary switch to 2. To restore the factory settings, press both buttons
simultaneously to change the LCD to 'do it' and hold both buttons for more than one
second. When the buttons are released, the LCD displays FAC A.
Range Inversion
Displays whether the device is operating with a normal or inverted range setting.
A normal range setting is where LRV (Menu 0E) is lower in value than URV (Menu 0F): the
LCD displays nor. An inverted range is where LRV (Menu 0E) is higher in value than URV
(Menu 0F): the LCD displays inv.
Rotary
Menu
Switch
Item
Position
19
9
1. Set the rotary switch to 9.
2. Press both buttons simultaneously for more than one second to toggle between
the two modes, effectively switching the values for LRV and URV.
Page 80
Left Arrow
Description
Factory Settings
On
Left Arrow
Description
On
Range Inversion
Pointek CLS500 – INSTRUCTION MANUA
LCD
Meaning
Display
No parameters
FAC A
changed from factory
setting
Range settings altered:
FAC P
timers and thresholds
unchanged
More parameters have
FAC ?
been changed
Mode
Values
normal
*
Display shows nor
inverted
Display shows inv
7ML19985GG03