Technical Specifications: Pointek Cls500 - Siemens Pointek CLS500 Operating Instructions Manual

Capacitance switches
Hide thumbs Also See for Pointek CLS500:
Table of Contents

Advertisement

Technical Specifications: Pointek CLS500

Power
Supply voltage
• maximum
• minimum
Loop current
Mounting
Location
Altitude
Ambient temperature
• standard
• ATEX-Explosion Proof
Relative humidity
Installation category
Pollution degree
Performance
Measurement range
Transmitter type
• MSP-2002-1
Minimum span
Measurement frequency
Accuracy
Repeatability
Temperature stability
7ML19985GG03
33 V DC
12 V DC at 3.6 mA (9.5 V DC at 22 mA)
3.6 to 22 mA / 22 to 3.6 mA (2-wire current loop)
indoor/outdoor
2000 m max.
-40 to +85
-40 to +70
-40 to +85
suitable for outdoor (Type 4X / NEMA 4X / IP65, IP68
enclosure)
I
4
1 to 330 pF
1 pF
420 kHz @ Cx = 0 pF
deviation <0.1% of actual measurement value
0. 1 % actual measurement
0.15 pF (0pF) or <0.25% (typically <0.1%) of actual
measurement value, whichever is greater over the full
temperature range of the transmitter
Pointek CLS500 – INSTRUCTION MANUAL
o
o
C (-40 to +185
F)
o
o
C (-40 to +158
F) for T6
o
o
C (-40 to +185
F) for T5 to T1
Page 5