Ge_Threshold; Le_Threshold - Satec Expertmeter PM180 Reference Manual

High performance analyzer, plc configurator
Hide thumbs Also See for Expertmeter PM180:
Table of Contents

Advertisement

2.3.4 GE
GE function returns TRUE if input IN1 greater or equal to IN2.
GE function is shown in the figure below.
2.3.5 EQ
EQ function returns TRUE if input IN1 equal to IN2.
EQ function is shown in the figure below.
2.3.6 LE
LE function returns TRUE if input IN1 less or equal to IN2.
LE function is shown in the figure below.

2.3.7 GE_THRESHOLD

GE_THRESHOLD function returns TRUE if input IN greater or equal to
OPERATE and returns FALSE if input IN less or equal to RELEASE.
In this function IN is a value input, OPERATE and RELEASE are inputs to
set threshold. Usually to set threshold locale variables are used.
GE_THRESHOLD function is shown in the figure below.

2.3.8 LE_THRESHOLD

LE_THRESHOLD function returns TRUE if input IN less or equal to
OPERATE and returns FALSE if input IN greater or equal to RELEASE.
In this function IN is a value input, OPERATE and RELEASE are inputs to
set threshold. Usually to set threshold locale variables are used.
8
Figure 3 - NOT
Figure 4 - GE
Figure 5 - EQ
Figure 6 - LE
Figure 7 - GE_THRESHOLD