Integrated website showing device and connection data
5.2
Accessing the Web server locally via the application interface
(10/100 BASE-T connector)
Prerequisites
Making a
connection to the
SINAUT MD740-1
website
86 von 105
•
A GPRS connection must be active, i.e. the LED C of the
SINAUT MD740-1 is lit and indicates that an IP address has
been assigned by the GPRS network.
•
NAT must take place for the address of the locally connected
computer that is to access the internal website (see Firewall #
NAT, page27).
•
The firewall of the SINAUT MD740-1 must allow the data
packets that the locally connected computer sends to the Web
server of the SINAUT MD740-1 to pass (see Firewall
Outgoing, page 29)
Example:
If the computer you are also using for the configuration of the
SINAUT MD740-1 (own address 192.168.1.2) is to have access
to the website stored in the SINAUT MD740-1, the settings are,
for example, as follows:
Setting for Firewall # NAT:
Possible address entries: 192.168.1.2 or 192.168.1.0/24
Setting for Firewall # Outgoing:
Prot. From IP
TCP 192.168.1.2
or
TCP 192.168.1.0/24
1. Start your Web browser, e.g. MS Internet Explorer.
Enter the address of the internal website in the browser's
address line. The address is:
http://192.168.0.8
Effect:
The start page of the website stored in the
SINAUT MD740-1 is displayed - see The website of the
SINAUT MD740-1 page 88.
2. Click on the hyperlink of the required HTML pages to view
them.
From Port To IP
any
192.168.0.8 any
any
192.168.0.8 any
#
To Port
Action
Accept
Accept
SINAUT MD740-1