Configuration
4.1

Network menu

Network # # # # Local
Local IP address of
the SINAUT MD740-
1 according to
default setting:
192.168.1.1
24 von 105
Internal IPs
An internal IP is the IP address at which the SINAUT MD740-1 can
be accessed by devices of the locally connected network.
The default setting for the IP address is as follows:
IP address:
Local netmask:
You can determine further addresses at which the
SINAUT MD740-1 can be accessed by devices of the locally
connected network. This is helpful if, for example, the locally
connected network is divided into subnets. In this case, several
devices from different subnets access the
SINAUT MD740-1 at different addresses.
! If you want to determine a further internal IP, click on New.
You can determine any number of internal IPs.
! If you want to delete an internal IP, click on Delete.
(The first IP address in the list cannot be deleted.)
Additional Internal Routes
If further subnets are connected to the locally connected network,
you can define additional routes.
See also Network example diagram, page 81.
! If you want to determine a further route to a subnet, click on
New.
Enter the following:
- the IP address of the subnet (network), and
- the IP address of the gateway via which the subnet is
connected.
You can determine any number of internal routes.
! If you want to delete an internal route, click on Delete.
192.168.1.1
255.255.255.0