2.4

WIRING THE RECORDER

2.4.1 Recommendations

All wiring must be in accordance with local norms and carried out by authorized experienced
#
personnel.
The ground terminal must be connected before any other wiring (and disconnected last).
#
A switch in the main supply is required near the equipment.
#
If an external fuse is used to protect the line supply to the recorder, the fuse should match the
#
recorder fuse rating (fuse type) as well as for the fuseholder.
Sensor wiring should be run as far as possible from power wiring.
#
To reduce stray pick-up, we recommend the use of twisted pair sensor wiring.
#
EMI effects can be further reduced by the use of shielded cable sensor wiring. The shield must be
#
connected to the ground terminal.
Note: Terminal (A) is only used for RTD. (See diagrams above.)
2-5