Technical data
Writing
Pen
Multipoint
Noise immunity
Safety protection
Electrical insulation
Input to input
Input to ground
Input to line voltage
Line voltage to ground
Alarm relay to ground
Logic input to ground
Temperature
Ambient
Storage
Humidity
Roll
Fanfold
Vibrations
5. PRODUCT SPECIFICATION SHEET
1 cartridge per pen, fiber tip, 1400 m of trace per color (blue, red,
green)
1 print wheel, 6 colors, 250 m of trace per color (purple, red, black,
green, blue, brown).
This product is in conformity with the protection requirements of the
following European council directives:
73/23/EEC – Low Voltage directive
89/336/EEC – EMC Directive
Conformity of this product with any other "CE Mark" Directive(s) shall
not be assumed.
EMC Classification:
EN 50081-2-1993 Electromagnetic Compatibility – General
Emission Standard, Part 2: Industrial Environment.
EN 50082-2-1995 Electromagnetic Compatibility – General
Immunity Standard, Part 2: Industrial Environment
Complies with IEC 61010-1 and UL 3121-1 for process control
instrumentation Pollution Degree 2, Installation category II.
Test voltage 280 Vac or Vdc for 1 minute (except for RTD input)
Test voltage 2.1 kVdc for 1 minute
Test voltage 2.1 kVdc for 1 minute
Test voltage 2.1 kVdc for 1 minute
Test voltage 2.1 kVdc for 1 minute
Test voltage 500 Vdc for 1 minute
0 to 50°C (32 to 122°F) for Fan Fold
0 to 60° C (32 to 140°F) for Roll Chart
-40 to 70°C (-40 to 158°F)
10 to 90% RH non-condensing
15 to 80% RH non-condensing
Frequency:
10 to 60 Hz, amplitude 0.07 mm
60 to 150 Hz, acceleration 1 g
5-5