The FS24X Plus™ 3IR Flame detector Electro-Optical Detector Module has pluggable terminal
blocks for interfaces (Power Supply, RS-485, Relay, etc.) with retention for easy wiring and for plug-
in replacement of a module in the field. The terminal block takes 14 AWG to 24 AWG cable with
stranded conductors. Typically 16 AWG or 2.5 mm2 shielded cable is recommended for all wiring.
When connecting to a fire panel, follow NFPA 72 standard. For duplicate terminals and leads for
supervised relay connections to the fire alarm system, use p/n FS24XP-NFPA-KIT NFPA assembly kit
include 6-pin two-row connector as well as 9-pin two-row connector.