FUNCTION
ALARM AN
DEFINITION :
HOW TO MODIFY IT :
POSSIBLE CHOICES :
SEE ALSO :
EXAMPLE :
7. DETAILED CONFIGURATION
PARAMETER
AL TYPE
Type of alarm (High, low, differential ...)
Select a new alarm type.
NONE : Select "none" for unused alarms.
ALARM HIGH : alarm to occur when the value equals or exceeds
the alarm setpoint.
ALARM LOW : alarm to occur when the value equals or is below
the alarm setpoint.
CHG RATE H : alarm to occur if the trace increases quicker than the
alarm setting (setpoint is given in eng.unit/second).
CHG RATE L: alarm to occur if the trace decreases quicker than the
alarm setting (setpoint is given in eng.unit/second).
CHG RATE H, L : alarm to occur if the trace increases/decreases
quicker than the alarm setting (setpoint is given in eng.unit/second).
DIFFERENTIAL : occurs if the absolute difference between the
values of the specified channel and a second channel exceeds the
alarm setpoint.
CH DIFF for DIFFERENTIAL in this function.
7-20