OSSD Timing Behavior

The SafeZone Mini device tests the OSSDs immediately after switch-on and
then at regular intervals. For this purpose, the SafeZone Mini device briefly
switches off both OSSDs (for 300 µs) and checks whether the OSSDs switch
to the OFF state during this time.
ATTENTION: Verify that the safety inputs on the controller that is used do
not respond to these test pulses and as a result cause the machine or system
to unintentionally shut down.
Figure 50 - Diagram of OSSD Test Pulses
40 ms
OSSD1
OSSD2
Approx.
35 ms
A
B
C
Approximately 35 ms after the switch-on of the OSSDs, the SafeZone Mini
device performs the first voltage test (A) and then after a half basic response
time (40 ms) it performs a second voltage test (B).
After another half basic response time of the SafeZone Mini device, there is a
shutdown test (C). 120 ms later another voltage test (D). Then, the SafeZone
Mini device performs a shutdown test (C) and a voltage test (D) alternately at
an interval of 120 ms.
duration for the individual tests.
Figure 51 - Voltage Test after Switching on the OSSDs
Approx. 650 s
<300 s
OSSD1
OSSD2
Rockwell Automation Publication 442L-UM005B-EN-P - April 2017
120 ms
120 ms
D
C
Figure
51,
Figure
52, and
Figure 53
<300 s
Technical Specifications
Chapter 11
120 ms
t
t
D
show the pulse