Error and Status
Indication —
Seven-segment Display
Table 15 - Error and Status Indication on the Seven-segment Display
Display
Possible Cause
Power-up cycle — all segments are
activated sequentially.
.
Object in protective field
Object in warning field 1
Object in warning field 2
Initialization of the device
.
Waiting for configuration or
.
configuration not completed
Waiting for restart of the device
.
Error of the external device monitoring
.
(EDM)
or
.
Error in the control switch for restart or
.
reset
SafeZone Mini device has a malfunction
or is faulty
Overcurrent on OSSD connection 1
Short circuit to 24V at OSSD connection 1 Check the wiring for short circuit to 24V.
This section explains the meaning of the error indications on the
seven-segment display and how to respond to the messages. You can find a
description of the positions and symbols on the SafeZone Mini device in
Indicators on page
23.

Lockout Operational Status

In case of certain faults or an erroneous configuration, the device can go into
the lockout operational status. The seven-segment display on the safety laser
scanner then indicates
operation, follow these steps:
1. Rectify the cause of the fault per
2. Switch off the power supply for the SafeZone Mini device, wait at least 3
seconds, and then switch back on the power supply.
Or, restart the safety laser scanner with the aid of the SCD software.
Corrective Action
No error
No error
No error
No error
The display goes out automatically when the SafeZone Mini device has been initialized and/or the connection to
the second device has been made.
If the display
does not go off:
.
• Check whether the partner device is in operation.
• Check the wiring.
If no partner device is connected:
Check the system configuration with the aid of the SCD software. Transfer the corrected configuration to the
SafeZone Mini device again.
The display goes off automatically once the configuration has been successfully transferred.
If the display
does not go off:
.
Check the system configuration with the aid of the SCD software. Transfer the corrected configuration to the
SafeZone Mini device again.
Switch off the voltage supply for the SafeZone Mini device for at least 2 seconds and then switch it back on.
• Check whether the contactors are working correctly or if they are wired incorrectly and rectify any error.
• If
is displayed: also switch off the voltage supply for the SafeZone Mini device for at least 2 seconds and
.
switch it back on.
• Check the functionality of the control switch. The button may be defective or permanently operated.
• Check the wiring of the control switch for short circuit to 24V.
Switch off the voltage supply for the SafeZone Mini device for at least 2 seconds and then switch it back on.
If the display does not go off:
Send the SafeZone Mini device to the manufacturer for repair.
• Check the switching element connected (contactor, relay). Replace, if necessary.
• Check the wiring for short circuit to 0V.
Rockwell Automation Publication 442L-UM005B-EN-P - April 2017
.
.
, , , , , , , , , or .
Table 15 on page
Diagnostics
Chapter 10
Status
To place the device back in
81.