Wiring in Accordance with EMC Regulations

The quality of the shield is dependent on the quality of the connection of the
screen. In principle, the best screening action can only be achieved with the
connection of the shield at both ends with large area connections.
If it is not possible to connect the screen via threaded fittings, connect the
screen physically close, for example, to a control cabinet chassis with a metal
clamp.
IMPORTANT If there is a PE in an installation, it can be used for the connection of the
functional earth connection (FE). However, an FE is never allowed to be used
as a PE.

Functional Earth

To achieve the specified EMC safety, the functional earth FE must be
connected (for example, to the central earth star point of the vehicle or system).

Round Plug Connector

Figure 38 - Round Plug Connector
8
6
7
1
(1)
Table 9 - Pin Assignment
Pin
Signal
1
WF
2
+24V DC
3
I/O1
4
I/O2
5
OSSD1
6
OSSD2
7
0V DC
8
FE/shield
Housing
FE/shield
(1) Use the cordsets that are listed in
Rockwell Automation Publication 442L-UM005B-EN-P - April 2017
5
4
3
2
Function
Output for warning field 1
Supply voltage
Universal I/O
Universal I/O
Output signal switching device
Output signal switching device
Supply voltage
Functional earth/shield
Functional earth/shield
Table 25 on page 95
to connect the SafeZone Mini device.
Electrical Installation
Chapter 5
63