The product warranty becomes invalid if the following safety precautions are not followed during handling,
installation, commissioning and general use/operation of Eltek power supply systems.
General Precautions
!
CAUTION: Even though the product incorporates protection circuitry and other safeguards, it can be damaged, perform poorly or
have a reduced lifetime if it is exposed to incorrect treatment during transport, installation or service. Always handle the equip-
ment using proper lifting techniques, do not roll, climb or drill hole in the cabinets or enclosures.
Device
Hazard
WARNING: Opening the equipment may cause terminal injury — even if the mains AC supply is disconnected. Hazardous voltages
may be present inside, as large capacitors may still be charged.
Electric
Shock
Environmental Precautions
CAUTION: To avoid damage the equipment, keep objects clear of system ventilation inlets, outlets and system fans, if any, ensur-
sss
ing the airfl ow through the units is not obstructed, and that the fans rotate freely. Use caution with power modules, as they can
reach extreme temperatures under load and normal operation.
Ventilated
Hot Surface
WARNING: The installer/user is responsible for ensuring that the power system is not damaged by current surges, over-voltages,
etc. caused by external transients, lightning, electrostatic discharge, etc. To avoid damage and obtain the expected system reli-
ability, it is mandatory to always install SPDs in Eltek's power supply systems. Follow the instructions given in "Guidelines for
Current Surge
Protection
Lightning and Surge Protection", doc. 2024623.
WARNING: The electronics in the power supply system are designed for indoor, clean environment. When installed in outdoor
enclosures — using heat sinks or closed loop heat management systems — it is important to maintain the equipment closed and
tight during operation, to avoid external air entering the enclosure. Also, when using open loop heat management systems, it is
Humidity & Dust
Protection
important to replace the fi lters on a regular basis. Indoor installations in dusty or humid areas require appropriate air fi ltering of
the room, or fi ltering of the air entering the power system. Follow the instructions given in "Generic Guidelines Environmental
Protection.", doc. 2038879
Precautions during Installation
!
CAUTION: Read the user documentation carefully before installing and using the equipment, as installation and operation is to
be performed as described in it. Always tighten screws and bolts with the torque values recommended in the documentation. For
safety reasons, the commissioning and confi guration of the equipment is only to be performed by Eltek's personnel or by author-
Qualifi ed
Personnel
ized and qualifi ed persons.
!
CAUTION: This product is tested and verifi ed according to international safety, environmental and EMC standards. Any non-Eltek
equipment installed into this product after delivery might infl uence the performance and could infringe the original approvals. The
installer is responsible for ensuring that the environmental properties of this product/ system do not deteriorate during installa-
EMC, NEC/CEC
Regard
tion, and that it is performed in accordance with applying regulations.
Installations in USA and Canada must comply with NEC/CEC requirements.
!
CAUTION: Before you start the electrical installation, you must always disconnect all external supply fuses, as well as internal
battery and load fuses/ breakers, if any.
Device
Hazard
WARNING: For safety reasons (high leakage current / high touch current) you must always connect the AC earth wire (PE) to the
terminals, before you connect the AC input cable(s).
Electric
The batteries, if any, represent a major energy hazard. To avoid short-circuit of battery poles, you must always remove metallic
Shock
objects — uninsulated tools, rings, watches, etc. — from the vicinity of the batteries.
2
SAFETY and ENVIRONMENTAL PRECAUTIONS
Quick Installation Guide • Chameleon 48V, 650W, HE, IP65, Stand-alone Module
Power Supply Systems
G1
G2
E1
E2
E3
I1
I2
I3
I4
Need help?
Do you have a question about the Chameleon Stand-alone and is the answer not in the manual?
Questions and answers