Type Of Conductor Connection - Siemens SIMOTICS SD Operating Instructions Manual

Low-voltage motors
Table of Contents

Advertisement

Electrical connection
6.3 Conductor connection
Table 6- 10
Table 6- 11
6.3.2

Type of conductor connection

Terminal board
Connection with cable lug
DIN 46 234
Bend down the cable lug for the
connection!
Connection of an individual
conductor with terminal clamp
Connection of two conductors of
approximately the same
thickness with terminal clamp
① Link rail
② Power supply cord
③ Motor connection cable
④ Cover washer
56
Max. conductor connection for explosion-proof machines (with the exception of Zone 22
and 1MJ) and VIK standard version
Frame size
56 ... 112
132
160
180
180 (1LG4, 1LG6)
200 ... 225
250 ... 280
315
Max. conductor connection for standard 1MJ machines
Frame size
71 ... 80
90 ... 160 M
160 L
180
200 ... 225
250 ... 280
315
Max. connectable conductor cross-section
[mm²]
4,0
6,0
16,0
10,0
16,0
50,0
120,0
240,0
Max. connectable conductor cross-section
[mm²]
4,0
6,0
16,0
25,0
50,0
120,0
240,0
Operating Instructions, 05/2014, 5 610 00000 02 000