6.6
Conductor connection
Cross-sections that can be connected depending on the size of the terminal (possibly
reduced due to size of cable entries)
Table 6- 4
6.6.1
Type of conductor connection
Terminal board
Connection with cable lug
DIN 46 234
Bend down the cable lug for the
connection.
Connection of an individual con-
ductor with terminal clamp
Connection of two conductors of
approximately the same thickness
with terminal clamp
①
Connecting bar
②
Line supply cable
③
Motor connecting cable
④
Cover plate
Standard motors SH 63 ... 355
Operating Instructions, 12/2018, A5E38483075A
Max. conductor connection
Shaft height
63 ... 90
100 ... 112
132
160 ... 180
200
225
250 ... 280
315
6.6 Conductor connection
Max. connectable conductor cross-section
[mm²]
1.5
2.5 with cable lug
4.0
6.0
16.0
25.0
35.0 with cable lug
120.0
240.0
Electrical connection
Conductor
cross-
section
[mm²]
... 25
... 10
... 25
71