Zone 1 With Ex E Iib Gb Type Of Protection (Increased Safety "E") - Siemens SIMOTICS SD Operating Instructions Manual

Low-voltage motors
Table of Contents

Advertisement

Operation
8.5 Class
8.5.3

Zone 1 with Ex e IIB Gb type of protection (increased safety "e")

158
82
II
2
1
CE - or EAC marking
Identification number or name of nominated testing agency
Code for prevention of explosions
Device group: II not for mining, but other hazardous zones
Device category: 2 for occasional danger
Atmosphere: G for gas
Explosion protection: International
Type of protection: "e" Increased Safety
Explosion group: IIB for ethylene
Temperature Class: T3 for maximum surface temperature of 200° C
Device protection level: Gb for a high level of protection in hazardous zones with
explosive gas mixtures
Zone 1
"X" special conditions
G
Ex
Ex
e
Operating Instructions, 05/2014, 5 610 00000 02 000
e
IIB
IIB
T3
T3
Gb
Gb
X
Low-voltage motors

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics gpSimotics dpSimotics xp

Table of Contents