Hirschmann RS20 series User Manual page 11

Industrial ethernet rail switch
Hide thumbs Also See for RS20 series:
Table of Contents

Advertisement

Relevant for use in explosion hazard areas (Hazardous
Locations, Class I, Division 2):
Relevant for North America for devices certified for Hazardous Locations:
Power, input and output (I/O) wiring must be in accordance with Class I,
Division 2 wiring methods [Article 501-4(b) of the National Electrical
Code, NFPA 70] and in accordance with the authority having jurisdiction.
SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C AND D
HAZARDOUS LOCATIONS, OR NON-HAZARDOUS LOCATIONS
ONLY.
WARNING – EXPLOSION HAZARD – SUBSTITUTION OF ANY
COMPONENTS MAY IMPAIR SUITABLE FOR CLASS I, DIVISION 2.
WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT
EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS
KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS.
The USB connector is for temporary connection only. Do not use,
connect, or disconnect unless area is known to be non-hazardous.
Connection or disconnection in an explosive atmosphere could result in
an explosion.
Peripheral equipment must be suitabel for the location it is used in.
Use 60/75 °C (140/167 °F) or 75 °C (167 °F) copper (Cu) wire only.
Avertissement - Risque d'explosion - Ne pas débrancher tant que le
circuit est sous tension à moins que l'emplacement soit connu pour ne
contenir aucune concentration de gaz inflammable.
Avertissement - Risque d'explosion - La substitution de tout composant
peut rendre ce matériel incompatible pour une utilisation en classe I,
division 2.
Installation RS20/22/30/32/40
Release 05 12/2015
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs22 seriesRs30 seriesRs32 seriesRs40 series

Table of Contents