UPS5000-A-(600 kVA-800 kVA)
User Manual (40 kVA)
Connect cables from bottom to top in this sequence: bypass input power cables, output
power cables, mains input power cables, and battery input cables.
When you connect each phase wire, tighten screws from inside to outside to secure wires.
1.
The hole size and quantity are for reference only.
(1) Signal cable tray cover
Issue 03 (2017-10-16)
Remove the power cable tray cover and signal cable tray cover from the bottom of the
cabinet. Use a hole saw to drill holes in the power cable tray cover, attach grommet strips
around the holes to protect cables, and reinstall the power cable tray cover on the cabinet,
as shown in
Figure 3-43
Figure 3-43 Removing cable tray covers from the bottom of the 600 kVA UPS
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
and
Figure
3-44.
(2) Power cable tray cover
3 Installation
81