UPS5000-A-(600 kVA-800 kVA)
User Manual (40 kVA)
Figure 4-27 Basic Param. screen
Advanced Parameter Settings
Figure 4-28
Issue 03 (2017-10-16)
Single/Parallel
Set the UPS running mode. The value can be Single (default) or Parallel.
Output voltage level (V)
Set the system output voltage level. The value can be 380 V, 400 V (default), or 415 V.
After you change the parameter value, the upper thresholds for the bypass voltage are
restored to the default values. If Output voltage level is 380 V or 400 V, the default
upper threshold is 15% and the default lower threshold is 20%. If Output voltage level
is 415 V, the default upper threshold is 10% and the default lower threshold is 20%. The
parameter is configurable after the inverter shuts down.
Output frequency (Hz)
Set the system output frequency level. The value can be 50 Hz (default) or 60 Hz.
Battery capacity (Ah)
Set the battery string capacity. The value range is 5 to 3000 Ah. The default value is 600
Ah for the UPS5000-A-600 kVA, 800 Ah for the UPS5000-A-800 kVA.
Number of cells
Set the number of cells. Each 12 V battery consists of six cells. The value range is
180–276, 192 by default.
A cell consists of electrodes and electrolytes, which is the basic unit for the battery. Each cell has a
nominal voltage of 2 V. A battery is a unit consisting of single or multiple cells in a shell. Each
battery has a nominal voltage of 2 V or 12 V. The number of cells must be a multiple of 12 (for
example, 180 and 192).
Cell float voltage, Cell equalized volt, Float volt. temp. comp. coef., and EOD voltage threshold
are set for cells.
to
Figure 4-30
show the Advanced Param. screen.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
143