UPS5000-A-(600 kVA-800 kVA)
User Manual (40 kVA)
Alarm
ID
(Alarm
ID-Cau
se ID)
0089-1
0090-1
0090-2
0356
0359
0332
0334
0334
0342
0343
Issue 03 (2017-10-16)
Alarm
Severity
Name
bypass
Rack output
Minor
overload
Dry contact
Critical
board fault
Battery
Minor
Mode
No power
Warning
supplied
Output
Minor
disabled
BSC master
Warning
system
BSC slave
Warning
system
Mains input
Critical
breaker
open
BPM input
Critical
breaker
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
UPS is not
mode.
normal, and
transfers to
bypass
mode.
The load is
Check the load. Remove some loads
excessive.
or expand the UPS power capacity if
the UPS is overloaded.
I2C
Replace the dry contact board
communicati
MUE05A.
on with the
dry contact
board
MUE05A
fails.
I2C
Replace the dry contact board
communicati
MUE06A.
on with the
dry contact
board
MUE06A
fails.
The UPS is
The running status is displayed. See
working in
details about how to handle other
battery
alarms.
mode.
No power is
The running status is displayed. See
supplied.
details about how to handle other
alarms.
The output is
The running status is displayed. See
disabled.
details about how to handle other
alarms.
BSC master
The running status is displayed. No
system.
further measures are required.
BSC slave
The running status is displayed. No
system.
further measures are required.
The mains
The running status is displayed. No
input circuit
further measures are required.
breaker is
OFF.
The bypass
The running status is displayed. No
input circuit
B Alarm List